Can I protect steelwork with Promat boards in a permanently exposed environment?
Promat structural steel fire protection boards are not designed to be left permanently exposed to the environment.
Promat offers two structural steel board solutions, Promatect®-XW for up to 60 minutes fire performance and Vermiculux®-S for up to 240 minutes, which can be left exposed for up to 6 months during the construction phase, subject to the following qualifications: the boards must not be left in standing or pooling water or be subjected to any water run-off from roof or slab structures above (protection can be provided by temporary waterproofing measures) and all cut edges should be sealed prior to installation to help prevent any long-term moisture ingress. This is particularly important when considering structural protection to perimeter/edge beams.
Further information regarding painting, sealing and decorative finishes can be found on our website within Technical Data Sheet 56.
Didn't find what you are looking for? Contact our Technical Support